Lab for performance rating of water-chilling packages
Description

 

Based on the testing method provided by standard GB/T 10870-2001 and ASHRAE30:1995, the lab can test performance of water-chilling (heat pump) packages. The liquid secondary coolant rating is used in main side, and heat balance method is used in auxiliary side. It meets the requirements of standard GB/T 18430.1 2001.

 

1. rated cooling capacity

2 rated heating capacity

3 the maximum load.

4. performance at low temperature

5 defrost performance 

 

1. testing temperature:

                                     under refrigeration working condition: evaporator water inlet: 5-15℃,

                                                                                                          condenser water inlet: 15-35℃

                                       under heat pump working condition : condenser water inlet:35-45℃,

                                                                                                          evaporator water inlet: 10-25℃

  3. Temperature control precision: ±0.1℃

  4. Repeatability precision: ±4%

  5. Precision of accuracy: ±2%

  6. Deviation between main side and auxiliary side: ±5%

7.control mode: manual or automatic control
 

(The above specifications are only for reference, It can be customized according to customer’s requirements.)